Trip Bus - GE T60 Instruction Manual

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning
them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning
such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista software under Settings > Protection
Summary. Navigate to a specific protection or control protection element and check the bus box by hovering over the
blank check box and selecting an option that displays. Once the required element is selected for a specific bus, a list of
element operate-type operands are displayed and can be assigned to a trip bus. If more than one operate-type operand is
required, it can be assigned directly from the trip bus menu.
The following settings are available.
— The trip bus output is blocked when the operand assigned to this setting is asserted.
TRIP BUS 1 BLOCK
— This setting specifies a time delay to produce an output depending on how output is used.
TRIP BUS 1 PICKUP DELAY
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
TRIP BUS 1 BLOCK:
Off
TRIP BUS 1 PICKUP
DELAY: 0.00 s
TRIP BUS 1 RESET
DELAY: 0.00 s
TRIP BUS 1 INPUT 1:
Off
TRIP BUS 1 INPUT 16:
Off

TRIP BUS 1

LATCHING: Disabled
TRIP BUS 1 RESET:
Off
TRIP BUS 1:
TARGET: Self-reset
TRIP BUS 1
EVENTS: Disabled
Figure 5-189: Trip bus fields in the protection summary
Range: FlexLogic operand
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: Enabled, Disabled
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Enabled, Disabled
CONTROL ELEMENTS
5
5-321

Advertisement

Table of Contents
loading

Table of Contents