GE T60 Instruction Manual page 445

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Five zones of phase distance protection with a minimum 150 ms time delay are provided as backup protection for
transformers or adjacent lines.
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to "Non-directional," the mho function becomes an
offset mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
The phase quadrilateral distance function has a reactance characteristic, right and left blinders, and 100% memory-
polarized directional and current supervising characteristics. When set to "Non-directional," the quadrilateral function
applies a reactance line in the reverse direction instead of the directional comparators.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
The
setting (common for the distance elements of all zones as entered under
SIGNAL SOURCE
ELEMENTS  SETTING GROUP 1(6)  DISTANCE
The
setting (common for the distance elements of all zones as entered under
MEMORY DURATION
GROUPED ELEMENTS  SETTING GROUP 1(6)  DISTANCE
The common distance settings described earlier must be chosen properly for correct operation of the phase distance
elements.
Although all zones can be used as either instantaneous elements (pickup [
time-delayed elements (operate [
tripping mode.
Ensure that the Phase VT Secondary Voltage setting (see the
 VOLTAGE BANK
action.
— All phase distance zones are reversible. The forward direction is defined by the
PHS DIST Z1 DIR
whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the forward reach
impedance defined by the
PHS DIST Z1 REACH
and
PHS DIST Z1 REV REACH
PHS DIST Z1 REV REACH RCA
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
PHS DIST Z1 QUAD
RGT BLD: 10.00 Ω
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
PHS DIST Z1 QUAD
LFT BLD: 10.00 Ω
PHS DIST Z1 QUAD
LFT BLD RCA: 85°
PHS DIST Z1
SUPV: 0.200 pu
PHS DIST Z1 VOLT
LEVEL: 0.000 pu
PHS DIST Z1
DELAY: 0.150 s
PHS DIST Z1 BLK:
Off
PHS DIST Z1
TARGET: Self-reset
PHS DIST Z1
EVENTS: Disabled
)
)
] FlexLogic operands), only zone 1 is intended for the instantaneous under-reaching
OP
menu) is set correctly to prevent improper operation of associated memory
and
PHS DIST Z1 RCA
as illustrated in the following figures.
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.000 to 5.000 pu in steps of 0.001
Range: 0.150 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
] and dropout [
PKP
DPO
SETTINGS  SYSTEM SETUP  AC INPUTS
settings, and the reverse reach impedance defined by
GROUPED ELEMENTS
SETTINGS  GROUPED
SETTINGS 
] FlexLogic operands) or
setting,
PHS DIST Z1 RCA
5-227
5

Advertisement

Table of Contents
loading

Table of Contents