PRODUCT DESCRIPTION
also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The T60 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
2
Table 2-1: ANSI device numbers and functions supported
Device
Function
number
21G
Ground distance
21P
Phase distance
24
Volts per hertz
25
Synchrocheck
27P
Phase undervoltage
27X
Auxiliary undervoltage
32
Sensitive directional power
49
Thermal overload protection
50/87
Instantaneous differential overcurrent
50BF
Breaker failure
50G
Ground instantaneous overcurrent
50N
Neutral instantaneous overcurrent
50P
Phase instantaneous overcurrent
50_2
Negative-sequence instantaneous overcurrent
51G
Ground time overcurrent
51N
Neutral time overcurrent
2-2
CHAPTER 2: PRODUCT DESCRIPTION
Device
Function
number
51P
Phase time overcurrent
51_2
Negative-sequence time overcurrent
59N
Neutral overvoltage
59P
Phase overvoltage
59X
Auxiliary overvoltage
59_2
Negative-sequence overvoltage
67N
Neutral directional overcurrent
67P
Phase directional overcurrent
67_2
Negative-sequence directional overcurrent
68
Power swing blocking
78
Out-of-step tripping
81O
Overfrequency
81R
Rate of change frequency
81U
Underfrequency
87RGF
Restricted ground fault
87T
Transformer differential
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL