Resetting
If the residual current device trips the molded case circuit breaker due to a high residual
current or actuation of the test button, the <RESET> button on the RCD is released. At the
same time, the trip alarm switch which is mechanically coupled with the <RESET> button
also signals that a trip has occurred.
The <RESET> button is labeled with the letter "R".
The following actions must be taken in order to reset the residual current device and reclose
the main contacts of the molded case circuit breaker:
1. Press the <RESET> button on the residual current device.
The "tripped" signal at the signaling contacts is canceled, the residual current device is
now reset.
2. Reset and switch on the molded case circuit breaker.
Note
The molded case circuit breaker cannot be switched on before the <RESET> button on the
residual current device has been actuated.
Parameterization of the residual current device
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
Setting button for response current I
Setting button for delay time Δt (RCD520 only)
Δn
Accessories
4.8 Residual current devices