Siemens 3wl Configuration Manual

Air circuit breakers
Hide thumbs Also See for 3wl:

Advertisement

Quick Links

Air Circuit Breakers
Totally Integrated Power – SENTRON
© Siemens AG 2015
Configu-
ration
Edition
Manual
10/2014
siemens.com/lowvoltage

Advertisement

loading

Summary of Contents for Siemens 3wl

  • Page 1 © Siemens AG 2015 Air Circuit Breakers Totally Integrated Power – SENTRON Configu- ration Edition Manual 10/2014 siemens.com/lowvoltage...
  • Page 2 © Siemens AG 2015...
  • Page 3 © Siemens AG 2015 3WL Air Circuit Breakers Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC General data - Design - Function - Configuration - Technical specifications Project planning aids - Characteristic curves...
  • Page 4 Parameters freely programmable CubicleBUS Standard -- Not available Optional ETU15B cannot be used with 3WL circuit breakers, size III. 3WL air circuit breakers/non-automatic air circuit breakers according to UL 489 up to 5000 A, see Catalog LV 16. Siemens · 10/2014...
  • Page 5: Breaking Capacity

    © Siemens AG 2015 3WL Air Circuit Breakers Introduction Breaking capacity Size Type 3WL11 3WL12 3WL13 Breaking capacity 3-pole 4-pole Rated short-circuit breaking capacity Rated operational voltage U Up to 415 V AC Rated operational voltage U Up to 500 V AC...
  • Page 6 3WL Air Circuit Breakers Introduction 3WL air circuit breakers: 3WL air circuit breakers are extremely flexible in use and offer consistent communication capability. With the 3WL circuit breakers, just three sizes cover a performance range of 630 A to 6300 A. All models are characterized by the same design, the same operation and the same comprehensive accessories.
  • Page 7 © Siemens AG 2015 3WL Air Circuit Breakers Introduction Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit) Ethernet PROFIBUS PROFINET CubicleBUS 3VA-line 3VA-line Measurement function Plus 3VA molded case circuit breakers 3VL molded case circuit breakers Zone Selective Interlocking module...
  • Page 8 Catalog LV 10, chapters "Mea- possibility of linking up external input and output modules to suring Devices and Power Monitoring" and "Software" the circuit breaker-internal CubicleBUS of the 3WL air circuit breaker • Innovative software products for parameterization, operation,...
  • Page 9 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Introduction • Preventive maintenance reduces the risk of expensive plant Benefits downtimes • Metering function with a very wide range of measured values, Low space requirements such as current, voltage, energy, power etc.
  • Page 10: General Data

    © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Design Circuit breaker Breaking capacity Dimensions With- rated current n max at 500 V AC (kA) or...
  • Page 11 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Safety and reliability Fixed-mounted circuit breakers To protect the circuit breakers and system against unauthorized switching and to protect the maintenance and operator person- nel, the system contains many locking devices.
  • Page 12 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Withdrawable short-circuit, grounding, and bridging units An energy storage device for shunt releases allows the circuit breaker to be opened even if the control voltage is no longer Portable positively-driven grounding and short-circuit devices available.
  • Page 13: Circuit Breakers

    © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Circuit breakers Arc chute Carrying handle Labeling plates Motor cutout switch (option) or "Electrical ON" (option) Name plate for circuit-breaker Spring charge indicator "Mechanical ON"...
  • Page 14 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Locking devices Sealing devices Locking device in OFF position Sealing cap for "Electrical ON" button This function prevents closing of the circuit breaker and The "Electrical ON button"...
  • Page 15 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Rated current coding unit between circuit breaker Equipment-dependent coding and guide frame Withdrawable circuit breakers and guide frames can be retrofit- Withdrawable circuit breakers and guide frames are equipped ted with an equipment-dependent coding unit.
  • Page 16 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Function NSE0_00950c ETU15B ETU25B ETU27B Functions of the Electronic Trip Units Basic protection functions Overload protection Short-time delayed short-circuit protection...
  • Page 17 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data ETU76B Rating Plug ETU45B ETU76B Siemens · 10/2014...
  • Page 18 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Electronic Trip Units (ETU) Tripped indicator/ Reset button The Electronic Trip Unit is controlled by a microprocessor and operates independently of an auxiliary voltage.
  • Page 19 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data ETU15B Electronic Trip Unit Application: Option: safety lock prevents pressing of Simple building and system protection without...
  • Page 20 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data ETU27B Electronic Trip Unit Application: Option: safety lock Classical building, motor and system protection with prevents pressing of reset button after time-selective coordination for up to 6300 A.
  • Page 21 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data ETU76B Electronic Trip Units Application: Mechanical RESET Option: safety lock The multi-talent with graphical display for system analysis –...
  • Page 22 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Measurement method Setting Vectorial summation current formation (measurement method 1) How the module is set depends on the measurement...
  • Page 23 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data 3WL circuit breakers for DC applications This version of the 3WL non-automatic air circuit breaker is suitable for direct current applications. The external protective device DIGmat S100 provides adjustable overload and short- circuit protection for the 3WL non-automatic air circuit breaker.
  • Page 24 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Communication-capable circuit breakers Ethernet PROFIBUS PROFINET CubicleBUS 3VA-line 3VA-line Measurement function Plus 3VA molded case circuit breakers...
  • Page 25 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Ethernet MODBUS TCP RS 485 with MODBUS RTU 3VA-line 3VA-line 3VA Molded Case Circuit Breakers COM100 breaker data server...
  • Page 26 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Communication-capable 3WL circuit breakers Function Electronic Breaker PROFIBUS Metering Analog Digital Digital Breaker Trip Unit version Status...
  • Page 27 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter All 3WL circuit breakers with ETU45B, ETU76B (CubicleBUS integrated)
  • Page 28 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data CubicleBUS modules Digital output module with rotary coding switch 6 items of binary information concerning the state of the circuit breaker (reasons for tripping and warnings) can be output via this module to external signaling devices (e.g.
  • Page 29: Technical Specifications

    © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Technical specifications Breaking capacity Size Type 3WL11 3WL12 3WL13 Breaking capacity 3-pole 4-pole Short-circuit breaking capacity Rated operational voltage U...
  • Page 30 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 Rated current I at 40 °C, at 50/60 Hz...
  • Page 31 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 Mounting position 30°...
  • Page 32 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63 Rated current I at 40 °C, at 50/60 Hz...
  • Page 33 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63 Mounting position 30°...
  • Page 34 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size I to III Type 3WL1 Manual operating mechanism with mechanical closing N  230 Closing/charging the stored- Max.
  • Page 35 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size I to III Type 3WL1 Auxiliary releases Shunt releases (ST) • For continuous command - Response value Pickup >...
  • Page 36 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Size I to III Type 3WL1 Ready-to-close signaling switch (S20) (acc. to DIN VDE 0630) Breaking capacity •...
  • Page 37 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Protection functions ETU15B ETU25B ETU27B Parameterization by D & S Function overview of the electronic trip system...
  • Page 38 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC General data Protection functions ETU45B ETU76B Parameterization by D & S Function overview of the electronic trip system Overload protection...
  • Page 39: Project Planning Aids

    © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Characteristic curves Every electronic trip unit type and every setting has its own 10000 characteristic curve. Only a selection is shown in the following.
  • Page 40 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Every electronic trip unit type and every setting has its own 10000 characteristic curve. Only a selection is shown in the following.
  • Page 41 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Dimensional drawings Voltage transformers for 3WL air circuit breakers External current transformers for N conductor without copper...
  • Page 42 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids CubicleBUS modules Breaker Data Adapter (BDA Plus) 3WL9 111-0AT2.-0AA0 3WL9 111-0AT33-0AA0 81,9 45,5 Siemens · 10/2014...
  • Page 43 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Door cutout for operator panel using protective cover IP55 Protective cover, IP55 4 x R5 4 x 5,5...
  • Page 44 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size I, up to 2000 A, fixed-mounted version, 3- and 4-pole Standard version Optional connection variants...
  • Page 45 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size I, up to 2000 A, withdrawable version, 3- and 4-pole Standard version Optional connection variants...
  • Page 46 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole Standard version Optional connection variants...
  • Page 47 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole Vertical connection 4000 A 85 Nm Ø...
  • Page 48 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size II, up to 4000 A, withdrawable version, 3- and 4-pole Standard version Optional connection variants...
  • Page 49 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size II, up to 4000 A, withdrawable version, 3- and 4-pole Vertical connection 4000 A / Terminal face...
  • Page 50 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size III, up to 6300 A, fixed-mounted version, 3- and 4-pole Standard version Optional connection variants...
  • Page 51 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Size III, up to 6300 A, withdrawable version, 3- and 4-pole Standard version Optional connection variants...
  • Page 52: Circuit Diagrams

    © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Circuit diagrams Terminal assignment diagram Internal wiring Terminals External wiring optional Accessories (Auxiliary switch S1, S2 = Standard)
  • Page 53 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Example of an overall circuit diagram for 3WL circuit breakers (3WL1. ..–..–4GN4–Z C11+ C22 + K07) signaling switch (option C22), with electronic trip unit LSING with undervoltage release"UVR"...
  • Page 54 © Siemens AG 2015 3WL Air Circuit Breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC Project planning aids Example of the mode of operation of Zone Selective Interlocking functionality in power distribution SENTRON 3WL...
  • Page 55 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) General data Technical specifications Size 3WL11 20 3WL12 10 Type 3WL12 20 3WL12 40 Rated current I at 40 °C A 2000 Main conductor ...
  • Page 56: Dimensional Drawings

    © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Project planning aids Characteristic curves 10000 = 0.4 ... 1.0 = 2 ... 10 s at 6 = 0.4 = 1.0 1000 = 1.25...
  • Page 57 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Project planning aids Size I, up to 2000 A, fixed-mounted version, 3- and 4-pole Standard version Optional connection variants Horizontal connection Front connection (single)
  • Page 58 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Project planning aids Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole Standard version Optional connection variants Horizontal connection Front connection (single)
  • Page 59 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Project planning aids Size II, up to 4000 A, withdrawable version, 3- and 4-pole Standard version Optional connection variants Horizontal connection Vertical connection up to 3000 A...
  • Page 60 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Project planning aids Circuit diagrams AC230 DC24 AC230 X1.2 X1.1 X5.2 X5.1 DIGmat S100 Auxiliary power „Emergency STOP” X2.1 X4.i1+ Shunt X4.i1-...
  • Page 61 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Project planning aids More information Up-to-date information on the Internet at: www.siemens.com/sentron Siemens · 10/2014...
  • Page 62 © Siemens AG 2015 3WL Air Circuit Breakers 3WL non-automatic air circuit breakers up to 4000 A (DC) Notes Siemens · 10/2014...
  • Page 63 © Siemens AG 2015...
  • Page 64 Availability and technical specifications are subject GERMANY to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners. www.siemens.com/lowvoltage...