Technical Details - Pilz 20 748-03 Operating Manual

Programmable safety systems pss-range pss sb active junction basis
Table of Contents

Advertisement

Technical details

Electrical data
Supply voltage
Tolerance range
Current consumption
Galvanic isolation
Connection
Sub branches
Virtual cable runs of an Active Junction
SafetyBUS p
Transmission rate
Cable runs
Transmission type
Mechanical data
Max. cross section of external conductors
Torque setting for connection terminals
Dimensions (H x W x D)
Weight
Environmental data
Protection type (EN 60529, 09/00)
Mounting position
Ambient temperature
(EN 60068-2-14, 11/99)
Storage temperature
(EN 60068-2-1/-2, 07/94, 03/93)
Climatic suitability
(DIN IEC 68-2-3, 12/86)
Condensation
Vibration (EN 60068-2-6, 04/95)
Shock (EN 60068-2-27, 03/93)
EMC
24 VDC
23.4 ... 30 VDC including residual ripple of
max. ± 1.2 V
120 mA plus load currents from the
sub branches (max. 6 A) and load currents for
fibre-optic couplers
(max. 25 mA per fibre-optic coupler)
Yes (optocoupler), between the
SafetyBUS p
®
main branch and the
sub branches
®
SafetyBUS
:
Male 9-pin D-Sub connector
Supply and sub branches:
4-pin screw connector
Max. 3 A load current per sub branch,
electronic short circuit protection,
integral terminating resistor (120 Ohm) per sub
branch
50 m
Max. 500 kBit/s
Max. 3500 m
Differential two-wire cable
2
1 x 2.5 mm
or 2 x 1.5 mm
Single-core or multi-core with
crimp connectors
1.2 Nm (screws)
94 x 49.2 x 126 mm
250 g
IP20
Any
0 ... +60 °C
-25 ... +70 °C
Max. 93 % r.h.
Not permitted
Frequency range: 10 ... 150 Hz
Amplitude: 0.075 mm, max. 1g
30g, 11 ms
EN 61000-6-2, 03/00
EN 55011, 05/00
2