Mitsubishi Electric MELSEC-L SSCNETIII/H User Manual page 98

Melsec-l series, head module
Table of Contents

Advertisement

Error
code
[SP. UNIT LAY ERR.]
• The number of connected modules exceeded 10.
• A module is installed in the position corresponding to the I/O
points of 4096 or greater.
• A module is installed across the boundary of 4096 I/O points.
2124
■Supplementary information
• Common information: 
• Individual information: 
■Diagnostic timing
• When powered on or reset
[SP. UNIT LAY ERR.]
• An inappropriate module was installed.
• No response is returned from the intelligent function module.
■Supplementary information
2125
• Common information: Module No. (Slot No.)
• Individual information: 
■Diagnostic timing
• When powered on or reset
[SYSTEM LAY ERR.]
An inappropriate module was installed.
■Supplementary information
• Common information: 
2170
• Individual information: 
■Diagnostic timing
• When powered on or reset
[PARAMETER ERROR]
In PLC Parameter, the number of points for empty slots is not set
within the range allowed for the head module.
■Supplementary information
3000
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[PARAMETER ERROR]
The parameters are corrupted.
■Supplementary information
3001
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[PARAMETER ERROR]
The parameter file is incorrect.
Or, the contents of the file are not parameters.
■Supplementary information
3004
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[SP. PARA ERROR]
The start I/O number for the intelligent function module set in GX
Works2 is different from the actual one.
■Supplementary information
3300
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[SP. PARA ERROR]
• Auto refresh parameters for the intelligent function module are
out of range.
• The intelligent function module set in GX Works2 is different
from the actually installed module.
3301
■Supplementary information
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
96
Error and cause
• Reduce the number of connected modules to 10 or less.
• Remove the module installed in the position corresponding to the I/O points of
4096 or greater.
• Replace the end module with a module so that the number of occupied points
does not exceed 4096.
• Reset the head module.
If this error occurs again, the hardware of the head module, I/O module,
intelligent function module, or END cover may be faulty. (Please consult your
local Mitsubishi representative.)
• Install an appropriate module.
• Reset the head module.
If this error occurs again, the hardware of the head module, I/O module,
intelligent function module, or END cover may be faulty. (Please consult your
local Mitsubishi representative.)
• Disconnect the inappropriate module.
• Reset the head module.
If this error occurs again, the hardware of the head module, I/O module,
intelligent function module, or END cover may be faulty. (Please consult your
local Mitsubishi representative.)
• Read detailed error information using GX Works2, and check and correct the
parameter corresponding to the value (parameter No.).
• Write the corrected parameters to the head module again, and reset or
reapply power to the head module.
If this error occurs again, the hardware of the head module may be faulty.
(Please consult your local Mitsubishi representative.)
• Read detailed error information using GX Works2, and check and correct the
parameter corresponding to the value (parameter No.).
• Write the corrected parameters to the head module again, and reset or
reapply power to the head module.
If this error occurs again, the hardware of the head module may be faulty.
(Please consult your local Mitsubishi representative.)
Check if the type of the parameter file is shown as "***.QPA" and if the file
contains parameters.
Correct the parameter setting.
Correct the parameter setting.
Action

Advertisement

Table of Contents
loading

Table of Contents