10.2

Periodic Inspection

This section describes items that must be inspected once or twice every 6 to 12 months.
The items must be inspected as well when the equipment has been relocated or modified, or wiring layout has been
changed.
Check box
The ambient temperature is within 0 to 55 C.
The ambient humidity is within 5 to 95%RH.
There is no corrosive gas.
The voltage across 100VAC terminals is within 85V to 132VAC.
The voltage across 200VAC terminals is within the range of 170V to 264VAC.
The voltage across 24VDC terminals is within 15.6V to 31.2VDC.
The modules are securely installed.
No dust or foreign matter is present.
No error has occurred.
82