(b) Grounding the cable clamp
Use shielded cables for external wiring and ground the shields of the external wiring cables to the control panel
with the AD75CK-type cable clamping (Mitsubishi). (Ground the shield section 20 to 30cm away from the
module.)
Inside the control panel
Module
AD75CK
For details of the AD75CK, refer to the following.
 AD75CK-type Cable Clamping Instruction Manual
(c) Connectors for external devices
When using connectors for external devices with any of the following modules, take the noise reduction
measures described below.
• High-speed counter module
• Flexible high-speed I/O control module
[Wiring example when using shielded cables]
The following figure shows the example of wiring using A6CON1 for noise reduction.
Connector
(A6CON1)
To the
module
20 to 30cm
External I/O device
The length between the connector
and the shielded cables should be
the shortest possible.
Shielded
cable
External I/O device
External I/O device
2
Ground the FG wire of 2 mm
shortest length. (Securely install the wire to
the control panel on the module side.)