Without ground rod:
Wire-Wrap Rear Panel
The
PWR-A and PWR-B terminal blocks. Figure 9 shows the location of
the terminal blocks, and Table D lists the terminal block pins.
Note:
available, connect the single office battery to the PWR-A terminal
block on the rear of the wire-wrap panel. This is not a recom-
mended arrangement.
Connect the power and frame ground wires to the terminals listed
in Table D, using appropriate sized spade lugs.
Note:
battery source, but do not apply the office battery to the Time-
Source 2700 at this time.
Table D. Wire-Wrap Panel Battery Terminal Block Pinouts
S
S
S
S
S
S
S
S
Crimp an appropriate-sized spade lug to the wire from pin 6 of
the DB9 connector, and secure the lug to a screw hole on the
rack. Remove the paint, and sand the area around the screw
hole, to ensure proper conductivity.
48 volt dc battery and frame ground enter through the
If two office battery supplies (battery A and battery B) are not
Connect the leads from the – and + terminals to the office
Pin
–48 V dc
+
Battery return
F
Frame ground
S
S
S
S
S
S
S
S
Signal
S
S
S
S
S
S
S
S
43