Installing The Braking Resistor - Siemens SINAMICS G130 Operating Instructions Manual

Braking module / braking resistor
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

3.4

Installing the braking resistor

The braking resistor should not be installed in the vicinity of the converter. The following
points must be taken into account:
● The braking resistors are only suitable for floor mounting.
● The maximum cable length between the Braking Module and braking resistor is 100 m.
● Sufficient space must be available for dissipating the energy converted by the braking
● A sufficient distance from flammable objects must be maintained.
● The braking resistor must be installed as a free-standing unit.
● Objects must not be placed on or anywhere above the braking resistor.
● The braking resistor should not be installed underneath fire detection systems, since
● For outdoor installation, a hood must be provided to protect the braking resistor from
CAUTION
A ventilation clearance of 200 m must be maintained on all sides of the braking resistor
(with ventilation grilles).
Figure 3-10
Dimension drawing for braking resistor (25 kW)
Braking Module / braking resistor
Operating Instructions, 03/2012, A5E00331454A
resistor.
these could be triggered by the resulting heat.
precipitation (in accordance with degree of protection IP20).
Mechanical installation
3.4 Installing the braking resistor
25

Advertisement

Table of Contents
loading