Disabling The Vdc-Max Controller - Siemens SINAMICS G130 Operating Instructions Manual

Braking module / braking resistor
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Integration of the thermostatic switch as release for switch-off via OFF2
The thermostatic switch must be connected to a free digital input of the SINAMICS G130 so
that the converter is safely disconnected from the power supply if the braking resistor
overheats. A digital input on the TM31 terminal module, on the TB30 Terminal Board or on
the Control Unit can be used for this
Subsequently the digital input must be used as release for a switch-off with OFF2. External
fault 2). The interconnection can be made with the STARTER or via the AOP30.
4.4

Disabling the Vdc-max controller

The Vdc-max controller must be switched off (p1240 = 0) when a brake chopper is used.
Braking Module / braking resistor
Operating Instructions, 03/2012, A5E00331454A
4.4 Disabling the Vdc-max controller
Connection
33