Installing Printers
Overview: Keltron Remote Printer (Model VS4095)
The VS4095 is a two-color (red and black), 40-column, 24 VDC printer that
can print up to 50 messages in 90 seconds. This printer connects to the EIA-
232 TB5 on the CPU and to the +24V screw on TB3 of AMPS-24/E, and
mounts in a separate cabinet next to the control panel. The VS4095 meets
UL fire and security requirements for an ancillary device; it is not ULC-
listed. For more information on the Keltron printer, contact the manufacturer
(Keltron Corp., Waltham, MA). Installation and configuration instructions follow.
NOTE: Depending on which version of the AMPS-24/E is being used, the terminal block
designations may differ from those listed. Please refer to the AMPS-24/E manual.
3.14.1 Printer Installation Sequence
1.
Fabricate a custom cable to connect a printer to the system. Length of the cable will vary with
each installation, but should not exceed a maximum length of 50 feet (15.24 meters). Printer
must be installed in the same room as panel. Using overall foil/braided-shield twisted-pair
cable, properly connect one end to the DB-25 Connector (provided) using the wiring
specifications shown in Figure 3.22.
2.
Tighten clamp on connector to secure cable. Connect the four open leads of the custom cable to
the TB5 terminal block on the CPU as shown in Figure 3.22.
DB-25 connector on
PRN Series Printer
Note: Outputs are power-limited
but are not supervised.
TB5 on Control Panel
3.
If installing a Keltron Printer VS4095/5, connect 24 VDC non-resettable power from a
UL-listed power supply to the Keltron printer as shown in Figure 3.22 (14 AWG).
4.
If installing a PRN series printer, plug it into your AC power source. Note: PRN printers
require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Because a secondary power source is not provided,
use a separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective
Signaling.
5.
Plug the DB-25 connector end of the custom cable into the EIA-232 port of your printer.
Tighten securely.
6.
Configure the printer as described in Section 3.14.2 "Configuring the Printer".
NOTE: Depending on which version of the AMPS-24/E is being used, the terminal block
designations may differ from those listed. Please refer to the AMPS-24/E manual.
NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014
DB-25 connector on
Keltron Printer VS4095/5*
7
4
3
2
TB5 on Control Panel
Figure 3.22 Printer Connections
Installation
Keltron Printer VS4095/5
power connections*
DC IN -
TB3 of AMPS-24/E
*Note: VS4095/5 is not ULC-listed.
DC IN +
39