RUGGEDCOM RSG2488
Installation Guide

Installing the Device

This section describes how to install the device, including mounting the device, installing/removing modules,
connecting power, and connecting the device to the network.
WARNING!
Radiation hazard — risk of serious personal injury. This product contains a laser system and is
classified as a CLASS 1 LASER PRODUCT. Use of controls or adjustments or performance of
procedures other than those specified herein may result in hazardous radiation exposure.
WARNING!
Electrocution hazard — risk of serious personal injury. Before performing any maintenance tasks,
make sure all power to the device has been disconnected and wait approximately 2 minutes for any
remaining energy to dissipate.
IMPORTANT!
This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall
render all warranties null and void.
Changes or modifications not expressly approved by RuggedCom Inc. could invalidate specifications,
test results, and agency approvals, and void the user's authority to operate the equipment.
IMPORTANT!
This product should be installed in a restricted access location where access can only be gained by
service personnel or users who have been instructed about the reasons for the restrictions applied to
the location and about any precautions that shall be taken; and access is through the use of a tool or
lock and key, or other means of security, and is controlled by the authority responsible for the location.
Section 2.1, "Mounting the Device"
Section 2.2, "Installing/Removing Power Supplies"
Section 2.3, "Connecting the Failsafe Alarm Relay"
Section 2.4, "Grounding the Device"
Section 2.5, "Cabling Recommendations"
Section 2.6, "Connecting to the Device"
Section 2.1

Mounting the Device

The RSG2488 is designed for maximum mounting and display flexibility. It can be ordered with connectors that
allow it to be installed in a 48 cm (19 in) rack, 2.5 cm (1 in) DIN rail, or directly on a panel.
Mounting the Device
Chapter 2
Installing the Device
3