RuggedCom RSG2488 Installation Manual page 39

Fully managed, industrial ethernet switch
Hide thumbs Also See for RSG2488:
Table of Contents

Advertisement

RUGGEDCOM RSG2488
Installation Guide
Test
IEC 1613/C37.90
IEC 1613/C37.90.1
IEC 1613/C37.90.2
IEC 1613/C37.90.3
NOTE
• In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during which no disturbance
errors will occur.
Table 11: Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-21-1
IEC 60068-21-2
EMI and Environmental Tests
Description
H.V. Impulse
Dialiectric Strength
H.V. Impulse
Oscillatory
Fast Transient
Earth Ground Ports
Radiated RFI
Enclosure Contact
ESD
Description
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
Vibration
Shock
Signal Ports
D.C. Power Ports
A.C. Power Ports
Signal Ports
D.C. Power Ports
A.C. Power Ports
Signal Ports
D.C. Power Ports
A.C. Power Ports
2.5 kV common
Signal Ports
D.C. Power Ports
2.5 kV common, 1 kV
diff. mode@1 MHz
A.C. Power Ports
Signal Ports
+/- 4 kV @ 2.5 kHz
D.C. Power Ports
A.C. Power Ports
Enclosure Ports
Enclosure Air
Test Ad
Test Bd
Test Db
Test Levels
Severity Levels
5 kV (Fail-Safe
Relay Output)
5 kV
5 kV (Fail-Safe
Relay Output)
5 kV
5 kV
2 kVAC
1.5 kVDC
2 kVAC
mode @1 MHz
+/- 4 kV
35 V/m
+/- 8 kV
+/- 15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
2g @ 10 - 150 Hz
30g @ 11 mS
Chapter 6
Certification
33

Advertisement

Table of Contents
loading