Gas supply
Gas pipe sizing must consider the gas input to this appliance as well as all other gas
appliances in the premises. The gas meter and regulator must be specified for the total
gas rate. An approved sizing chart such as the one in AS/NZS 5601.1 should be used.
The gas supply termination is inside the heater and enters through the rear of the
appliance.
Gas supply location
Mark off the location for the vertical centre line of the heater enclosure
. To the right of the vertical centre line, mark off the vertical and
horizontal locations for the gas supply penetration.
INBUILT
Masonry
305 mm to right of the
appliance centre line
45 mm from base of
enclosure
Terminate 230 mm from
front of enclosure
STEP 1
Inbuilt installations
The length of the gas supply termination
is measured from the front of the
enclosure.
Gas connection
Gas supply pipe
Installer, terminate to suit
12 | Neo installation guide: 11906-F 06-14
Mock chimney
305 mm to right of the
appliance centre line
45 mm from base of
enclosure
Terminate 230 mm from
front of enclosure
Freestanding installations
4
The length of the gas supply termination
is measured from the back of the heater
plus 125 mm.
Brass adaptor
½ " BSPT
FREESTANDING
Console
305 mm to right of the
appliance centre line
140 mm from floor level 215 mm from floor level
Terminate at wall
clearance plus 125 mm
4
Flexi
Gas supply location
1
2
Plinth
305 mm to right of the
appliance centre line
Terminate at wall
clearance plus 125 mm
STEP 2
5
Installer to terminate to suit, and fit
supplied gas connection . Leak test the
joint between the flexible gas connection
and termination.
3