Establishing Communication To The Instrument; Configuring The Instrument - AEMC Model 6292 Quick Start Manual

Micro-ohmmeter
Table of Contents

Advertisement

Establishing Communication to the Instrument

1.
Connect the instrument to the PC with the supplied cable.
2.
Double-click the Micro-Ohmmeter icon in the DataView folder that was cre-
ated on the desktop during software installation to open the Control Panel.
3.
From the menu bar, select Instrument, then click Connect to open the Con-
nection dialog box.
The instrument name should appear in the Communication port field. If not,
select it from the drop-down list. Ensure that the Instrument model field is set
to 6292, and the Communication rate is set to 57600. Then click OK.

Configuring the Instrument

Establish a connection to the instrument. Then from the menu bar, select Instru-
ment, then click Configure. The Configuration Panel dialog box will appear:
This dialog box allows you to configure options for each of the following settings:
Object name is the name of the test object. This name can be up to 20
characters in length.
Test duration determines how long the test will run. Selecting Unlimited will
run the test until you manually stop it by pressing the STOP button on the
instrument. Select Limited if you want the test to have a defined end point.
When you choose this option, the Duration field activates so you can enter
the number of seconds you want the test to run. The minimum is 5 seconds,
the maximum is 120 seconds.
Operating mode determines whether the test is run using BSG (both sides
grounded) or Normal mode.