Specifications - Altronix AL602ULADAJ Installation Manual

Nac power extender
Hide thumbs Also See for AL602ULADAJ:
Table of Contents

Advertisement

Altronix AL602ULADAJ is an extremely cost effective 6.5A remote power supply/battery charger. It may be connected to
any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as
strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system acces-
sories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, X, Y or Class A, Style Z
NAC loop circuits. Additionally, a separate 1.0A auxiliary output for four (4)-wire smoke detectors is available. The 6.5A
max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5A
max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be
programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output).
An individual output of 4A is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for
Class A, Style Z and/or Class B, Style W, X, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP
will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C,
NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally
closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control
supervision and power delivery to any combination of the four (4) outputs.
Agency Listings:
• UL Listed Control Units and Accessories for
Fire Systems (UL 864).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
• NFPA 72 Compliant.
Input:
• Power input 120VAC 60 Hz, 4A.
• Two (2) Class A, Style Z or two (2) Class B,
Style W, X, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• 24VDC @ 6.5A max total alarm current.
• 2.5A max current per output.
• Separate 1.0A auxiliary output.
• Two (2) outputs may be paralleled for more power on an
indicating circuit (see 02 Application Guide).
• Programmable supervised indicating circuit outputs:
Four (4) Class B, Style W, X, Y or Two (2) Class A,
Style Z or One (1) Class A, Style Z and Two (2) Class B,
Style W, X, Y (see 02 Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when
AC Fails.
• Zero voltage drop when switching over to
battery backup.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.
- 2 -
AL602ULADAJ - NAC Power Extender
Overview:

Specifications:

Supervision:
• AC fail supervision (form "C" contact, 1A / 28VDC).
• Instant local AC trouble reporting relay
• Battery presence and low battery supervision
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• 2-wire horn/strobe Sync mode allows audible
• Sync protocols include Potter/Amseco, Faraday,
• Temporal Code 3, Steady Mode, Input to Output
• Compatible with 24VDC fire panels.
• Output loop supervision steered to input 1 or input 2.
• Signal circuit trouble memory (helps identify
• Common trouble input and output for external trouble
• Ground fault detection.
• Unit includes power supply, red enclosure, cam lock,
Enclosure Dimensions (approx. H x W x D):
18" x 14.5" x 4.5" (457.2mm x 368.3mm x 114.3mm).
Factory set for 30 seconds with optional 2.5 to 3 hour
delay setting (field selectable).
(form "C" contact, 1A / 28VDC).
(form "C" contact, 1A / 28VDC).
notification appliances (horns) to be silenced
while visual notification appliances (strobes)
continue to operate.
Gentex
, System Sensor
®
Follower Mode (maintains synchronization of
notification appliances circuit).
intermittent loop problems).
signals tie-in.
and battery leads.
, and CooperWheelock
®
.
®
AL602ULADAJ