20.5 Connections for Intrinsically Safe
Operation
See section 17 HAZARDOUS AREA CERTIFICATIONS for
entity parameters and control drawing reference.

STARTUP

21

21.1 Quick Start Instructions

Once the positioner is installed, adjusting the DIP switch
settings and performing a Quick-Cal function will typically
get the positioner working properly. This simple procedure
takes only seconds for most valves.
1
Using the Configuration Switches, select the desired
configuration.
2
Hold the Quick-Cal button for 3 seconds. This will
initiate a stroke calibration.
After the stroke calibration is complete, the positioner is
ready for control.
flowserve.com
®
Logix
3200MD+ Digital Positioners FCD LGENIM0110-0 05/16
CAUTION: During the QUICK-CAL operation the valve
may stroke unexpectedly. Notify proper personnel that the
valve will stroke, and make sure the valve is properly
isolated.

21.2 Local User Interface Overview

®
The Logix
3200MD+ local user interface allows the user to
calibrate, configure the basic operation, and tune the
response of the positioner without additional tools or
configurators.
found.25.
Configuration Switches (8) – Used to set basic
configuration. See explanations in section 0
Configuration Switch
Interface Buttons – Used to calibrate the positioner,
perform special functions and navigate the display menu.
►QUICK-CAL / ACCEPT
o
▲Up
o
▼Down
o
◄Back
o
Selectable GAIN Switch (Rotary) – Used to manually
fine-tune the performance.
LED Indicators (Red, Yellow, and Green) – Indicate
status, alarms and warnings.
27
See Error! Reference source not
Settings
.