Communication Dipswitches - Omron GRT1-ML2 Manual

Smartslice communication unit
Hide thumbs Also See for GRT1-ML2:
Table of Contents

Advertisement

Hardware reference
LED
Description
Color
Status
TS
SmartSlice I/O
N/A
Not Lit
system com-
munication
status
Green
Flashing
(every
second)
Flashing
(every
0.5 sec-
ond)
Lit
Red
Flashing
Lit
Lit for 2 s Failure occurred while restoring settings to
UNIT
Green
Not Lit
PWR
Lit
I/O
Green
Not Lit
PWR
Lit
GRT1-ML2 MANUAL
Meaning
No power supply
Communication with SmartSlice I/O
Unit has not started
Overcurrent detected
SmartSlice I/O Unit added to the system
Backup/Restore function operating:
Restoring settings to SmartSlice I/O
Unit, backup function operating
Downloading SmartSlice I/O Unit set-
tings
Communication with SmartSlice I/O Unit
established
Non-fatal communication error occurred.
Communication timeout
Verification error occurred with regis-
tered table
Different model unit detected after
SmartSlice I/O Unit replacement
Fatal communication error occurred.
I/O unit or downloading I/O unit settings
No power supply to the unit
(All LEDs are off)
Power supply to the unit
No power supply to the SmartSlice I/O (No
output from the SmartSlice I/O Units, even
when they are in operation)
Power supply to the SmartSlice I/O
When the power of the Trajexia system is turned on, the TJ1-
MC__ executes its startup sequence before it initializes the
MECHATROLINK-II bus. During this startup sequence, the ML
COM LED is off.
When the TJ1-MC__ initalizes the MECHATROLINK-II bus
with the command MECHATROLINK(unit,0), the ML COM
LED goes on.
When the GRT1-ML2 loses the MECHATROLINK-II communi-
cation with the master, or when the command
MECHATROLINK(unit,1) is executed, the ML COM LED goes
off.
1.1.3

Communication dipswitches

/i
Dipswitch Function
Setting Description
1
MECHATROLINK-II
ON
address range
OFF
2
MECHATROLINK-II
OFF
bus speed
3
Frame size
OFF
4
HOLD/CLEAR
ON
OFF
1. Trajexia only supports 10 Mbps bus speed. Therefore always set
dipswitch 2 to OFF.
2. Trajexia only supports 32-byte communication. Therefore always set
dipswitch 3 to OFF.
70 hex − 7F hex
60 hex − 6F hex
1
10 Mbps
2
32 bytes
HOLD: All outputs hold their values when com-
mication is lost
CLEAR: All outputs become 0 when communi-
cation is lost
4