Event number
Message, cause and corrective measures
1304
Grid connection installation fault
Assignment of the line conductors of the external energy source to the AC2 connections of
the Sunny Island does not result in a right-rotating magnetic field.
Corrective measures:
1402
Grid fault
The voltage of the generator or the utility grid at the master is outside the configured thresh-
olds (redundant measurement).
Corrective measures for a generator:
Corrective measures for a utility grid:
1403
Grid fault
The Sunny Island disconnects from the external energy source because the voltage at con-
nection AC2 is too high or the battery voltage is too low.
Corrective measures:
1404
Grid fault
The Sunny Island disconnects from the utility grid due to phase conductor failure/overload at
terminal AC2.
Corrective measures:
1405
Grid fault
A short circuit is present at connection AC2 of the Sunny Island at line conductor L1 / L2 /
L3.
Corrective measures:
Operating Manual
• Ensure that the master is connected to L1, slave 1 is connected to L2, and slave 2 is
connected to L3.
• Adjust the thresholds for the voltage of the generator on the Sunny Island (see
Section 7.8.1.2, page 97). As an aid to this, observe and evaluate the measured values
Voltage external power connection phase Lxx during ongoing operation.
• If possible, adjust the generator voltage.
• Contact the Service (see Section 19, page 189).
• Contact the Service (see Section 19, page 189).
• Reduce the total power of the loads, e.g. by staggering their use over time.
• Ensure that there is not a short circuit present at connection AC2.
• Eliminate the short circuit.
15 Troubleshooting