SECTION 5 Modbus Communications Procedure

■ Variable Write, Single/Operation Command

5-14
This function performs operations such as writing to the variable area
(single) and operation commands (Communications Writing, RUN/
STOP, Bank Change, AT Execute/Cancel, Write Mode, Save RAM Data,
Software Reset, Move to Setup Area 1, Move to Protect Level, Auto/
Manual Switch, Initialize Settings, Alarm Latch Cancel, SP Mode, Invert
Direct/Reverse Operation, Program Start, and Infrared Communications
Use).
Writing is enabled in only the Two-byte Mode.
Command Frame
Slave
Function
Write variable
address
code
address
H'06
1
1
2
Response Frame
Slave
Function
Write variable
address
code
address
H'06
1
1
2
(1) Write variable address
Specify the address of the setting data that is to be written. For details
on addresses, refer to Section 6 Communications Data for Modbus.
For an operation command, specify 0000 or FFFF.
(2) Command Code and Related Information
Command
Command content
code
00
Communications writ-
ing
01
RUN/STOP
02
Bank change
03
AT execute/cancel
04
Write mode
05
Save RAM data
06
Software reset
Write data
CRC-16
2
2 bytes
CRC-16
Write data
2
2 bytes
Related information
00: OFF (disabled)
01: ON (enabled)
00: Run
01: Stop
00: Bank 0
01: Bank 1
02: Bank 2
03: Bank 3
04: Bank 4
05: Bank 5
06: Bank 6
07: Bank 7
00: AT cancel
01: 100% AT execute
02: 40% AT execute
00: Backup mode
01: RAM write mode
00
00