Detailed Description Of The Services; Read Variable Area - Omron E5CN-H Communications Manual

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

2.3 Detailed Description of the Services

■ Read Variable Area

This service reads data from the variable area.
Service Request PDU
Variable
Read
MRC SRC
type
start address
0
1 0
1
2
2
2
Service Request PDU
Response
MRC SRC
code
0
1 0 1
2
2
4
(1) Variable Type and Read Start Address
For details on variable types and read start addresses, see SECTION 3
Communications Data for CompoWay/F and SYSWAY.
(2) Bit Position
The E5CN/AN/EN-H does not support bit access. Fixed to "00."
(3) Number of Elements
Number of elements
0000
Double
0001 to 0019
word
(1 to 25)
Word
0001 to 0032
(1 to 50)
(4) Response Code
Normal Completion
Response code
0000
Normal completion
Error Occurred
Response code
1001
Command too long
1002
Command too short
1101
Area type error

2.3 Detailed Description of the Services

Bit
Number of
position
elements
0 0
4
2
4
Read data (for number
of elements)
Number of elements
× 8 or 4
Processing
The read operation is not performed (read data
is not appended to the service response PDU),
and processing ends in "normal completion."
Up to 25 elements (H'19) are read, and pro-
cessing ends in a normal completion.
Up to 50 elements (H'32) are read, and pro-
cessing ends in a normal completion.
Name
No errors were found.
Error name
The command is too long.
The command is too short.
The variable type is wrong.
Description
Cause
2-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-hE5an-h

Table of Contents