Performance Specifications; Physical Specifications - Emerson Rosemount 8742C Reference Manual

Magnetic flowmeter transmitter with foundation fieldbus and magnetic flowmeter flowtube
Table of Contents

Advertisement

Rosemount 8742C
Performance
Specifications

Physical Specifications

A-8
(System specifications are given using the frequency output and with the unit
at referenced conditions.)
Accuracy
Rosemount 8705 with 8712D, 8732C, or 8742C
±0.5% of rate from 1 to 30 ft/s (0.3 to 10 m/s). Includes combined effects
of linearity, hysteresis, repeatability, and calibration uncertainty. Accuracy
is ±0.005 ft/s (±0.0015 m/s) from low-flow cutoff to 1.0 ft/s (0.3 m/s).
Rosemount 8707 with 8712D/H, 8732C, or 8742C
±0.5% of rate from 3 to 30 ft/s (1 to 10 m/s). Include combined effects of
linearity, hysteresis, repeatability and calibration uncertainty. Accuracy is
±0.015 ft/s (±0.0045 m/s) from low-flow cutoff to 3.0 ft/s (1 m/s).
Vibration Effect
IEC 60770-1
Mounting Position Effect
None when installed to ensure flowtube remains full
Non-Wetted Materials
Flowtube
AISI Type 304 SST
Flanges
Carbon steel, AISI Type 304/304L SST,
or Type 316/316L SST
Housing
Welded steel
Paint
Polyurethane
Process Wetted Materials
Lining
PFA, Teflon (PTFE), Tefzel (ETFE), polyurethane, neoprene, Linatex
Electrodes
316L SST, Hastelloy C-276, tantalum, 90% platinum-10% iridium, titanium
Process Connections
ASME B16.5 (ANSI) Class 150, Class 300,
Class 600, or Class 900
0.5- to 30-inch (Class 150)
0.5- to 24-inch (Class 300)
0.5- to 10-inch (Class 600 derated to 1000 psi max)
1- to 8-inch (Full rated Class 600 and 900)
Reference Manual
00809-0100-4793, Rev CA
August 2004