Hardware Documentation Updates

This section contains late-breaking hardware information and corrections that
became known after the documentation set was published.
TABLE 2-1
Hardware Documentation Updates
TABLE 2-1
Title
SPARC Enterprise M3000 Server
Site Planning Guide
SPARC Enterprise M3000 Server
Installation Guide
12
Sun SPARC Enterprise M3000 Server Product Notes for XCP 1090 • August 2009
lists known documentation updates.
Page Number
Update
TABLE
2-5
It describes the power cord type for Hong Kong as "IEC
60320 C14" which should be modified as "BS1363."
The following note will be added.
Note - For servers that have the B-type plug,
confirm that a 15A overcurrent protection device is
available outside the server. If one is not available,
prepare an external 15A overcurrent protection that
can be achieved by means of no-fuse breakers
(NFBs) or fuses. The B-type plug refers to plugs
other than grounding-type ones with two parallel
blades, such as the NEMA L6-30, L6-20, L6-15, and
L5-15.
TABLE
2-5
It describes the power cord type for Hong Kong as "IEC
60320 C14" which should be modified as "BS1363."
The following note will be added.
Note - For servers that have the B-type plug,
confirm that a 15A overcurrent protection device is
available outside the server. If one is not available,
prepare an external 15A overcurrent protection that
can be achieved by means of no-fuse breakers
(NFBs) or fuses. The B-type plug refers to plugs
other than grounding-type ones with two parallel
blades, such as the NEMA L6-30, L6-20, L6-15, and
L5-15.
2-4 "Power Cords and Connector Types"
2-4 "Power Cords and Connector Types"