Negative Phase Sequence Overcurrent (46Nps) - Siemens 7SR12 Argus Manual

Overcurrent relay energy management
Hide thumbs Also See for 7SR12 Argus:
Table of Contents

Advertisement

2.11 Negative Phase Sequence Overcurrent
I
L1
I
L2
I
L3
Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:
Where two NPS elements are being used with different settings, it is convenient to test the elements with the
highest settings first. The elements with lower settings can then be tested without disabling the lower settings.
The Thermal withstand limitations of the current inputs, stated in the Performance Specification should always be
observed throughout testing.
NPS Overcurrent can be tested using a normal 3P balanced source. Two phase current connections should be
reversed so that the applied balanced 3P current is Negative Phase Sequence.
If Phase Rotation ACB is selected in the CT/VT Config menu, the expected PPS and NPD are exchanged and
the output from a standard positive sequence test set will be considered as NPS.
©2017 Siemens Protection Devices Limited
37
(x2)
(I
)
A
37
(x2)
(I
)
B
37
(x2)
(I
)
C
46
BC
I
(I
)
4
G
27
V
(V
)
59
L1
A
(x4)
27
V
(V
)
59
L2
B
(x4)
27
V
(V
)
59
L3
C
(x4)
Figure 2-12
Negative Phase Sequence Overcurrent
n/a
I
(I
), I
(I
), I
L1
A
L2
B
51, 51V, 51C, 37, 49, 50CBF, 60CTS, 46BC
46IT/46DT - Self Reset
7SR11 & 7SR12 Commissioning and Maintenance Guide
67/
67/
50
49
51V
50
51
BF
(x4)
(x4)
67/
67/
50
49
51V
50
51
BF
(x4)
(x4)
67/
67/
50
49
51V
50
51
BF
(x4)
(x4)
46
67/
67/
60
60
NPS
50N
51N
CTS
VTS
(x2)
(x4)
(x4)
67/
67/
50BF
50
51
SEF
SEF
NOTE: The use of some
functions are mutually exclusive
47
81
59N
(x2)
(x4)
(x2)
Optional
79
(I
),
L3
C
(46NPS)
7SR12
81
HBL
51c
2
81
HBL
51c
2
81
HBL
51c
2
64H
Note:
Example shows
Voltage Config =
Van, Vbn, Vcn
74
T/
CCS
Chapter 6 Page 39 of 72

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sr11 argus

Table of Contents