Virtual Input/Outputs; Figure 2-11 Binary Output Logic - Siemens 7SR12 Argus Manual

Overcurrent relay energy management
Hide thumbs Also See for 7SR12 Argus:
Table of Contents

Advertisement

Notes on Self Reset Outputs
Self reset operation has a minimum reset time of 100ms
With a failed breaker condition the relay may remain operated until current flow is interrupted by an upstream
device. When the current is removed the relay will then reset and attempt to interrupt trip coil current flowing via
its output contact. Where this current level is above the break rating of the output contact an auxiliary relay with
heavy-duty contacts should be utilised in the primary system to avoid damage to the relay.
Notes on Hand Reset Outputs – 86 Lockout
Any binary output can be programmed to provide an 86 lockout function by selecting it to be hand reset. Hand
reset outputs can be reset by either pressing the TEST/RESET► button, by energising a suitably programmed
binary input, or, by sending an appropriate command over the data communications channel(s).
On loss of the auxiliary supply hand-reset outputs will reset. When the auxiliary supply is re-established the binary
output will remain in the reset state unless the initiating condition is still present.
Notes on General Pickup
An output, General Pickup, is available to indicate that the pickup level has been exceeded for one or more
protection functions. Any protection function can be mapped to trigger this output in the OUTPUT
CONFIG>PICKUP CONFIG menu.
Logic signals,
e.g. '51-1'
BO 1
OUTPUT CONFIG>
OUTPUT MATRIX
(Or gates)
BO n

2.10 Virtual Input/Outputs

The relays have 8 virtual input/outputs, these are internal binary stores. By assigning the status of data items like
starters, alarms, equations etc. to a virtual input/output, the status of these items can be used to fulfil higher levels
of functionality.
The status of various data items can be assigned to virtual inputs/outputs using the INPUT CONFIG > OUTPUT
MATRIX menu.
Virtual input/outputs can be used as inputs to various functions - including blocks, inhibits, triggers, alarms etc. -
using the INPUT CONFIG > INPUT MATRIX menu.
Virtual input/outputs can also be used as data items in equations.
The status of the virtual inputs and outputs is volatile i.e. not stored during power loss.
©2017 Siemens Protection Devices Limited
Reset LEDs & Outputs (TEST/RESET key, Binary Input, Data Comms)
Hand Reset
BO 1 hand reset
≥1
OUTPUT
CONFIG>
BINARY
OUTPUT
CONFIG
BO n hand reset
≥1

Figure 2-11 Binary Output Logic

7SR11 & 7SR12 Description Of Operation
&
≥1
Min Operate Time
&
OUTPUT
CONFIG>
BINARY
OUTPUT
CONFIG
&
≥1
&
Output 1
S
Q
Event
R
&
Output n
S
Q
Event
R
&
Chapter 1 Page 27 of 88