Environmental Performance; General - Siemens 7SR12 Argus Manual

Overcurrent relay energy management
Hide thumbs Also See for 7SR12 Argus:
Table of Contents

Advertisement

7SR11 & 7SR12 Performance Specification
1.5

Environmental Performance

General

1.5.1
1.5.1.1
Temperature
IEC 60068-2-1/2
Type
Operating range
Storage range
1.5.1.2
Humidity
IEC 60068-2-78
Type
Operational test
1.5.1.3
Transient Overvoltage
IEC 60255-5
Type
Between all terminals and earth, or
between any two independent circuits
1.5.1.4
Insulation
IEC 60255-5
Type
Between any terminal and earth
Between independent circuits
Across normally open contacts
1.5.1.5
Installation Category
IEC 60255-27
Type
Installation Category (Overvoltage Category)
1.5.1.6
Pollution
IEC 60255-27
Level
Pollution Degree 2
1.5.1.7
IP Ratings
IEC60529
Type
Installed with cover on
Installed with cover removed
©2017 Siemens Protection Devices Limited
Level
-10 °C to +55 °C
-25 °C to +70 °C
Level
56 days at 40 °C and 93 % relative humidity
Level
5.0 kV, 1.2/50 µs 0.5j
Level
2.5 kV AC RMS for 1 min
1.0 kV AC RMS for 1 min
Level
Class III
Level
Rear
IP 10
Front
IP 51
Rear
IP 10
Front
IP 20