Ethernet Network Redundancy Iec 61850; Rstp - Rapid Spanning Tree Protocol - Siemens 7SR12 Argus Manual

Overcurrent relay energy management
Hide thumbs Also See for 7SR12 Argus:
Table of Contents

Advertisement

7SR11 & 7SR12 Installation Guide
6.3

Ethernet Network Redundancy IEC 61850

The EN100 module is used on Reyrolle devices to provide Ethernet/IEC61850 functionality. The EN100 supports
RSTP, PRP & HSR redundancy protocols.
All 7SR11 and 7SR12 IEC61850 variants are delivered with the EN100+ (Plus) module and firmware 4.21 or later.
The earlier EN100 (standard) modules are not used in the 7SR11 and 7SR12.
The EN100 module firmware can be updated by connecting to the relay via the rear Ethernet port. For more
information on connecting to the relay via the Ethernet port, please see the Reydisp Manager User guide.
Depending on the EN100 module type and Firmware version, the following protocol options are available:
Interface Type
Electrical RJ45 EN100+
Electrical RJ45 EN100+
Optical EN100+
Optical EN100+
6.3.1 RSTP – Rapid Spanning Tree Protocol
RSTP is a redundancy protocol with a minimal response time that has been standardized in IEEE-802.1D (2004).
The reconfiguration time depend on the topology and start at 50ms.
RSTP need to be enabled on the device within Reydisp Manager (See Reydisp Manager user guide). Network
rings with up to 30 devices is possible.
Chapter 5 Page 30 of 32
EN100
Firmware
4.08 or earlier
4.21and later
4.08 or earlier
4.21and later
Table 2: EN100 Redundancy availability
Figure: 6.3-1 RSTP Ethernet Network Ring Configuration
Line Mode
RSTP
OSM
©2017 Siemens Protection Devices Limited
Switch Mode
PRP
HSR

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sr11 argus