Signal Processing - Siemens SITRANS LR560 Operating Instructions Manual

Radar
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

2.3.6.2.
Defines the maximum rate at which the reported sensor value is allowed to
increase. Allows you to further adjust the SITRANS LR560 response to
increases in the actual material level. Fill Rate is automatically updated
whenever Response Rate (2.3.6.1.) is altered.
Options
Related parameters
Enter a value slightly greater than the maximum vessel-filling rate, in units
per minute.
2.3.6.3.
Defines the maximum rate at which the reported sensor value is allowed to
decrease. Adjusts the SITRANS LR560 response to decreases in the actual
material level. Empty Rate is automatically updated whenever Response
Rate (2.3.6.1.) is altered.
Options
Related parameters
Enter a value slightly greater than the vessel's maximum emptying rate, in
units per minute.

2.4. Signal Processing

Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
2.4.1. Near Range
The range in front of the device (measured from the sensor reference point
within which any echoes will be ignored. (This is sometimes referred to as
"Blanking" or "Dead Zone".)
Values
Related parameters
1)
Flange face: see
7ML19985LT01
SITRANS LR560 (PROFIBUS PA) – OPERATING INSTRUCTIONS
Fill Rate/Min
Empty rate/Min
Range: 0 to 999999 m / min.
Response Rate (2.3.6.1.)
* Medium
Level Unit (2.3.2.)
Dimensions on page 12
Range: 0 to 999999 m / min.
Response Rate (2.3.6.1.)
Slow
* Medium
Fast
Level Unit (2.3.2.)
Slow
Fast
Range: 0 to 105 m (0 to 344.5 ft)
Default: 0.278 m (0.91 ft)
Unit (2.3. 1 .)
.
Fill Rate
0. 1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
Empty Rate
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
1)
)
Page 69