Technical data

Power supply
Power supply
Current drain
Dissipation loss typ.
Presence detection
Type
Range
Brightness measurement
Type
Range
Note
Control elements
1 learning button
Display elements
1 red LED
Connections
KNX
10 / 12
Update: http://www.siemens.com/gamma-td
January 2015
via KNX
approx. 10 mA
approx. 0.24W at DC 24 V
Passive infrared (PIR)
horizontal 360°, vertical approx. 105°, 288 sectors
The detection range is divided in following areas:
Table 1 shows the maximum reachable diameter in meter
of the different areas for different installation heights (M).
.
5.0m
4.0m
3.5m
3.0m
2.5m
Contrast measurement
20...1000 Lux
Recommended mounting height for constant light level
control : 2.4 m – 3.0 m
for switching between normal operating mode and
addressing mode
for monitoring bus voltage and for displaying normal
mode/ addressing mode
This LED indicates motion during test mode.
Bus terminal
UP 258E22, UP 258D12, UP 255D21
ã Siemens AG 2015
Subject to change
A)
sitting in working desk height (0.8m)
B)
walking straight to the detector
C)
walking across the detector
and
D)
Area of the brightness measuring in working
desk height (0.8m)
M
A
B
-
8.5
-
7.5
5.5
6.5
5
6
4.5
5
Building Technologies Division
Control Products and Systems
P.O. Box 10 09 53, D-93009 Regensburg
C
D
14
Ø3.0
12
Ø2.3
10
Ø2.0
8
Ø1.6
7
Ø1.2