Mounting / Installation
5.12

Cable entry

1
2
!
30°
1
The conductor loops must be placed flat in the base
bottom.
2
The conductor loops must not be placed over this
zone, as otherwise the detector cannot be inserted
correctly.
3
Screwless connection terminals
4
Bare length 6.5 ... 7.5 mm
68
Building Technologies
Fire Safety & Security Products
The detector bases include a spring clip (admissible wire/strand cross-section
0.28... 1.5 mm
). Only one wire is allowed to be connected per terminal. This is the
2
only way in which a faultless connection can be guaranteed.
7
Cable entry in detector base
3
4
5
Contact for test tips
6
Turn the screwdriver 90° in the direction of the arrow
(left) to only loosen the conductors and insert the strand.
7
Optimum insertion of the wire without tool, at an angle of
approx. 30°
5
6
007004_k_en_--
16.04.2009