S600+ Instruction Manual

5.13 Enabling USB

5.14 Exporting Reports (USB)

5-14
Select a report based on the following options:
Option
Configuration
Reports
Communications
Current Alarms
Logs
Abort Printing
The enhanced CPU module has a Universal Serial Bus (USB) port that
you can use to export reports, alarms, events, and history data to a USB
flash drive. The port is disabled (locked) when delivered from the
factory.
To unlock the USB port and enable its use:
1.
Cold start the S600+.
2.
Select Factory Setup from the Cold Start menu.
3.
Select USB LOCK.
4.
Select DISABLE to unlock the USB port and allow the export of
any data to a flash drive.
: The USB port is available after you restart the configuration.
Note
The enhanced CPU module has a USB port. You can attach a USB
flash drive to the port and use an option on the front panel to export
report, event, or alarm history reports to the flash drive.
: This option is also available through the webserver.
Note
To export reports:
1.
Insert a flash drive in the USB port.
2.
Select TECH/ENGINEER from the Main Menu.
Select USB from the Tech/Engineer menu. The USB Report
3.
Control menu displays (see the screen sequence in Figure 5-15).
Front Panel
Sub Reports
1 Constant Log TXT
2 Constant Log CSV
3 Display Dump
4 Security Dump
5 All Alarms
1 Current Report
2 Config Report
3 Archived Reports
1 Modbus Maps
No sub-options; prints a list of current alarms to the
designated terminal or serial printer.
1 Alarm Log

2 Event Log

No sub-options; stops printing.