11.3 PIECE BIAS setting
▶ It displays Section Input Compensation.
▶ It explains for CH1, and CH2 is same as CH1.
Sensor measurements
After calibration, the current indicated value
Input Comp.
INRL
Point 1
▶ Calculation method by Compensation Section
① Compensated Temperature between Low Limit ~ Input Comp. Point 1 Section
= Actual Sensor Temperature + Input Comp. 1 Value
② Compensated Temperature between Input Comp. 1 ~ Input Comp. 2 Section
= Actual Sensor Temperature + (Actual Sensor Temperature – Input Comp. Point 1) X
③ Compensated Temperature between Input Comp. 2 ~ Input Comp. 3 Section
= Actual Sensor Temperature + (Actual Sensor Temperature – Input Comp. Point 2) X
④ Compensated Temperature between Input Comp. 3 ~ Input Comp. 4 Section
= Actual Sensor Temperature + (Actual Sensor Temperature – Input Comp. Point 3) X
2nd Edition of TEMP2000M_Series IM : April. 8. 2014
Input Comp.
Input Comp.
Input Comp.
Point 2
Point 3
(Input Comp. 2 Value – Input Comp. 1 Value)
(Input Comp. Point 2 – Input Comp. Point 1)
(Input Comp. 3 Value – Input Comp. 2 Value)
(Input Comp. Point 3 – Input Comp. Point 2)
(Input Comp. 4 Value – Input Comp. 3 Value)
(Input Comp. Point 4 – Input Comp. Point 3)
Input Comp.
Point 4
Point 5
Input Comp.
Input Comp.
Input Comp.
Point 6
Point 7
+ Input Comp. 1 Value
+ Input Comp. 2 Value
+ Input Comp. 3 Value