www.weg.net
PROG
DEF
Filter maintenance
2)
P1050
0
P1051
5,000h
2)
P1052
Ready parameter
Notes: Δ Setting depends on application.
1) Set P1050 in "0" to reset the operation time for ilter maintenance alarm.
TIMER ON
2)
P1052
Operation time for filter maintenance
Time ON when the VFD is running
P1051
Filter maintenance time (hours)
Notes: 1) A0770 will be generated on keypad during motor deceleration and the fault
F0771 after stopping the motor.
2) Set P1050 in "0" to reset the operation time for ilter maintenance alarm.
10
CFW700 HVAC-R Drives
Filter Maintenance Alarm
Warns about the need to replace
the filter.
User
Description
0 = disable
1 = enable and generates only alarm (A0770)
Δ
2 = enable and generates fault (F0771)
Filter maintenance time (0 to 32,000h)
Operation time for ilter maintenance
1)
P1050 = 1
A0770
Alarm
Do not
stop the
system
P1050 = 2
F0771
1)
FAULT
Stop the
system