Energy Saving - WEG CFW701 Quick Setup Manual

Hvac-r drives
Table of Contents

Advertisement

www.weg.net
Energy (%)
120
100
80
60
40
20
0
10
30
Valve
VFD
CFW701 with energy saving enable
PROG
DEF
Energy saving (V/F operation mode)
P0407
0.68
1)
P0588
0
P0589
3)
40
4)
P0590
600
P0591
10
Notes: ■ Set as per motor nameplate data.
1) Set to 0% disables the energy saving function.
2) Recommended value. Other values can be used depending on the
application and the motor.
3) Avoid the motor stalling.
4) The histeresis for the minimum speed level is 2 Hz.
12
CFW700 HVAC-R Drives

Energy Saving

Depending on the motor speed and load
conditions, flux is reduced decreasing
losses and therefore efficiency
is improved.
50
70
Flow (%)
User
Description
Motor rated power factor
60
2)
Maximum torque (0 to 85%)
40
2)
Minimum voltage level (40 to 80%)
2)
360
Minimum speed (360 to 18,000 rpm)
10
2)
Energy saving histeresis
Fans and pumps
applications
90
100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents