Fire Mode - WEG CFW701 Quick Setup Manual

Hvac-r drives
Table of Contents

Advertisement

www.weg.net
PROG
DEF
P0269 - DI7 function
P0269
0
Set to Fire Mode with logic level "0" (0 V) at DI7
P0580 - Fire Mode configuration
P0580
0
P0581 - Fire Mode PID setpoint
P0581
0
Deine the setpoint to be used by Fire Mode when the PID is enabled and P0580 = 3
P0582 - Fire Mode Auto-Reset configuration
P0582
0
Deine Auto-Reset for critical fault: Overvoltage (F022), Overcurrent/Short-circuit (F070)
and Safety Stop Relays (F160)
P0340 - Auto-Reset time
P0340
0
Reset itself automatically after the time set in P0340 has elapsed
Note: Δ Setting depends on application.
6
CFW700 HVAC-R Drives

Fire Mode

This function makes the drive to inhibit
its internal faults making the motor run
at adverse conditions without stopping
the process.
User
Description
24
24 = Fire Mode
0 = disabled (Fire Mode inactive)
1 = enabled (keeps speed reference/PID setpoint)
2 = enabled (set speed reference to maximum P0134)
Δ
3 = enabled (set PID setpoint to the value
programmed in P0581)
4 = enabled (disables the output,
motor will coast to stop)
Δ
-32,768 to 32,767
0 = limited (as deined in P0340)
Δ
1 = unlimited (every 1s)
Δ
0 to 255s
Alarm A211
will be generated
on keypad
when Fire Mode
is enable.