Ha input/output module ai-di 16/dq16x24vdc hart ha
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

The I/O module supports the following functions:
● Firmware update
● I&M identification data
● Parameter reassignment in RUN
● Value status QI
● IO redundancy
● HART communication (rev. 5 to rev. 7) in mixed mode
● Up to 8 HART variables in the input area
● Up to 4 multiHART ranges in the input/output area
● Output disable switch
You can configure the I/O module with HW Config and integrate it into your system.
Output disable switch
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds for the I/O module to be de-energized. After the output disable switch has been
pressed for 3 seconds, the LED DIAG flashes red, the LED MT lights up yellow and the I/O
module generates a diagnostics message. See section Status and error displays of the I/O
module AI-DI 16/DQ16x24VDC HART HA (Page 31).
Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.
Accessories
The following accessories must be ordered separately:
● Labeling strips
● Color-coded labels
● Reference identification label
● Shield connector
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
Manual, 05/2017, A5E39294170-AA
2.1 Properties of the I/O module AI-DI 16/DQ16x24VDC HART HA
Product overview
9