Drivers, parameters, diagnostics messages and address space
A.2 Parameter assignment
Error_
Error_
Cause
Code_
Code_
1
2
0xE1
0x01
Reserved bit set
0xE1
0x02
Invalid diagnostics enable bit set for operating mode
0xE1
0x03
Invalid hardware interrupt enable bit set for operating
mode
0xE1
0x04
Invalid value for hardware interrupt limit
0xE1
0x07
Invalid coding for input delay
0xE1
0x08
Invalid coding for interference frequency suppres‐
sion / integration time
0xE1
0x09
Invalid coding for smoothing
0xE1
0x0B
Invalid coding for pulse stretching
0xE1
0x0E
Invalid redundancy parameter assignment
0xE1
0x10
Invalid measurement type
0xE1
0x11
Invalid measuring range
0xE1
0x21
Wrong number of HART repetitions
Valid parameters
Only the values specified in the following are permitted. Values that are not listed are rejected
by the module.
Every parameter data record is checked by the module. If an incorrect parameter is detected,
the entire data record is rejected and the parameters of the module remain unchanged.
56
Solution
Check and correct the parameters
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
Manual, 05/2017, A5E39294170-AA