Analog value display

C.1

Representation of analog values in the current measuring ranges

Display/measuring range
The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table C-1
Table C-2
Table C-3
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
Manual, 05/2017, A5E39294170-AA
Current measuring range 0 to 10 mA
Values
Dec.
Hex.
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
0
Current measuring range 0 to 20 mA
Values
Dec.
Hex.
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
0
Current measuring ranges 4 to 20 mA and 4 to 20 mA with HART
Values
Dec.
Hex.
32767
7FFF
32511
7EFF
27649
6C01
Current measuring range
0 to 10 mA
>11.76 mA Overflow
11.76 mA Overrange
10 mA Nominal range
7.5 mA
1
361.69 nA
0
0 mA
Current measuring range
0 to 20 mA
>23.52 mA Overflow
23.52 mA Overrange
20 mA Nominal range
15 mA
1
723.4 nA
0
0 mA
Current measuring range
4 to 20 mA
>22.81 mA Overflow
22.81 mA Overrange
C
Range
Range
Range
93