Diagnostics Messages And Maintenance Events - Siemens SIMATIC ET 200SP HA Manual

Digital input module di 8x230vac ha (6dl1131-6gf00-0pk0)
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events
Figure A-3
Configuration byte x to x+1 for the channels 0 to 7
A.4

Diagnostics messages and maintenance events

Diagnostics messages
A diagnostic message is generated for each diagnostic event and the DIAG LED on the DI
8x230VAC HA flashes red or the MT LED lights up yellow.
The diagnostic messages can be read in the diagnostics buffer of the CPU, for example.
Diagnostic messages are assigned channel-specific to an input or assigned as module
messages to all inputs. All channels are switched off for diagnostic messages that affect the
entire module. Only the corresponding digital input is affected by diagnostic messages, which
refer to individual channels.
Table A-1
Diagnostics alarms, their meanings and corrective measures
Diagnostics mes‐
Error code
sage
Parameter as‐
10
H
signment error
Channel/compo‐
1F
H
nent temporarily
unavailable
Retentive memo‐
154
H
ry in carrier mod‐
ule defective
Retentive memo‐
155
H
ry in the terminal
block defective
Only the terminal blocks (TB 45 ...) are suitable for operating I/O modules with IO redundancy.
1
Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED
lights up on the module.
30
Assignment
Meaning
Module
● Parameter assignment does not
match the terminal block used
● Incorrect parameter assignment
Module
Firmware update is currently in pro‐
gress or has been canceled. The
module does not read any process
values in this state.
Module
An error of the memory block on the
adapter module was detected during
startup
Module
An error of the memory block on the
terminal block was detected during
startup
[ID: 91089678859]
Solution
● Correct the parameter
● Check terminal block
● Restart the firmware
● Wait for firmware update
Replace carrier module
Replace terminal block