Change Word Order:Enable/Disable (Even module only)
●
Example 1:
If the user wants to read a Modbus digital input module (DI module), Device ID is
1, data address is 10010~10019, and data count is 10.
In this case, the user can select an "Input Relay/Coil=> 2 Bytes module", module
parameters are shown in the below:
Input Relay/Coil module parameters:
Modbus Slave Device ID(M):1
●
Start Address(M):9
●
NO. Of Relay/Coil(M):10
●
Module Type(M):Read DI
●
Example 2:
If the user wants to write a Modbus analog output module (AO module), Device
ID is 2, data address is 40001~ 40004 and data count is 4.
In this case, the user can select an "Output Register => 4 Words module", module
parameters are shown in the below:
Output Register module parameters:
Modbus Slave Device ID(M):2
●
Start Address(M):0
●
Change Word Order:Disable
●
PS:
a. Relay/Coil module is digital module (DI/DO module), the unit is Byte;
Register module is analog module (AI/AO module), the unit is Word.
b. Modbus Slave Device ID:It is a Modbus slave device address.
c. Start Address:The GW-7552-B / GW-7552-M and Modbus slave device
exchange data from this starting address.
d. NO. of Relay/Coil:It is data size that the GW-7552-B / GW-7552-M and
Modbus slave device exchange.
e. Module Type:The user can select data type for data exchange by this
setting.
Write DO(WDO)-- Write Digital Output
Write AO(WAO)-- Write Analog Output
GW-7552-B / GW-7552-M PROFIBUS/MODBUS GATEWAY User Manual (Version 1.60, May/2017) PAGE: 37