Contact us If you encounter any problems while operating this device, feel free to contact us via mail at: service@icpdas.com . We guarantee to respond within 2 working days. GW-2139M (Modbus TCP to BACnet MS/TP Gateway) User Manual Version 1.0.0 Page:...
The most common use of the protocols at this time are for Ethernet attachment of PLC’s, I/O modules, and gateways to other simple field buses or I/O networks. GW-2139M (Modbus TCP to BACnet MS/TP Gateway) User Manual Version 1.0.0 Page:...
(MS/TP) protocol is used to relay and exchange information between building devices. GW-2139M contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) gives you flexibility in mapping Modbus TCP registers to any combination of BACnet objects.
2.2 Appearance LED Indicator Ethernet Port The GW-2139M is equipped with a RJ45 port for Ethernet LAN connection. When 100BASE‐TX is operating, the 10/100M LED is lit orange. When 10BASE‐T is operating or the machine is not connected to the network, it is turned off. When an Ethernet link is...
2.3 LED Indicator There are six LEDs to indicate the various states of the GW-2139M. The following is the illustration of these six LEDs. Figure 2.1 LED position of the GW-2139M LED Name GW-2139M Status LED Status ALL LEDs FW Updating Mode LED will be twinkled sequentially.
2. RS-485:D+ & D- (MSTP wiring) 3. RS-232:TxD / RxD / GND (Debug Port ; N, 8, 1 ; 115200 baud rate) 4. Ethernet:Connect the GW-2139M and computer into the same LAN through cable or Ethernet Switch/Hub. 5. INIT:Connect to GND to initial mode. (Address IP:192.168.255.1) 6.
3.2 GW-2139M Utility Please change the GW-2139M to initial mode and follow the following steps to set up the communication between the utility and the GW-2139M. Step0: Power off the GW-2139M. Step1: Pin INIT Connect to GND and Power on to initial mode.
- Update Tool: Please refers to -> http://www.icpdas.com/root/product/solutions/industrial_communication/fieldbus/bacnet_ ip/gateway/gw-2139m.html. 2) Short the FW with P.GND of GW-2139M and turn on the power. When the six LEDs of GW-2139M turn blinking alternately, the GW-2139M is successfully entered the firmware updating mode.
Page 17
3) Execute “FW_Update_Tool.exe” with the administrator privileges ( ) and follow the steps as Figure 3.3: In "Download Interface", select a network port for connecting to GW-2139M In "Firmware Path", select the latest firmware update file (GW2139M_xxxx.fw). In "Firmware Update", click “Update” to start the firmware updating.