configure the common parameters to set the communication mode and data format
by the PROFIBUS configuration tool. The common parameters are described
below.
COM Port baud rate:2400/4800/9600/19200/38400/57600/115200
COM Port parity:None/Even/Odd
COM Port data length:7/8 data bit
COM Port stop bit:1/2 stop bit
Modbus Type:Master/Slave
Modbus Format:RTU/ASCII
I/O Safe Mode:Retain last value/Switch safe value
Byte Order : Little-Endian/Big-Endian
Output Data Mode : Manual/Auto
Modbus Device ID(S):1~247
Polling Modbus Device Interval(ms) (M):1~65535ms
Query Message Timeout Value(ms)(M):1~65535ms
PS:
a. When stop bit of Com Port is 2, data bit of Com Port must be 7 or else stop bit
of Com Port will be set to 1.
b. I/O Safe Mode
When GW-7552-B / GW-7552-M acts as a Modbus master (Modbus
Type=Master):
i. Data exchange between Profibus master and GW-7552-B / GW-7552-M is
interrupted
"I/O Safe Mode" will be activated when the data exchange between
Profibus master and GW-7552-B / GW-7552-M is interrupted (e.g. no
physical connection, Profibus master leaves the data exchange mode, etc.).
 I/O safe mode = "Switch Safe Value"
The GW-7552-B / GW-7552-M will set internal DIO and AIO data to
safe value and send the safe values to the Modbus slave device.
 I/O safe mode = "Retain Last Value"
Internal DIO and AIO data retain last value
ii. Connection between Modbus slave and the GW-7552-B / GW-7552-M is
interrupted
 I/O safe mode = "Switch Safe Value"
The GW-7552-B / GW-7552-M will set the internal DI and AI data to
safe value and send safe values to Profibus master device.
 I/O safe mode = "Retain Last Value"
GW-7552-B / GW-7552-M PROFIBUS/MODBUS GATEWAY User Manual (Version 1.60, May/2017) PAGE: 34