Monitoring and Reporting on External Events

Trap message generated
and appears in trap log.
Alarm Module Configuration window reports
status input change from closed to open.
Figure 2-5. Monitoring and Reporting on External Events (Example)
®
PSAX 4500 Alarm Module User Guide, Issue 1
PacketStar
255-700-598
• Reports the change in state to the CPUn module
The local and remote alarm cutoffs operate independently of each other. This
change in state (on to off, off to on) is also shown in the Audible Alarm Sta-
tus panel of the console Alarm Configuration window.
A CO, remote switch room, or hut contains a number of sensors that monitor
environmental conditions, power availability, moisture, and so on. The 4500
Alarm module has 15 input sensors that monitor the activity or state change
of these external sensors (through relay contact open or close conditions),
and report the status of them to the NOC through trap messages and the
Alarm Module Configuration window. An example of a remote sensor would
be a door sensor that indicates whether the door is open or closed as shown
in Figure 2-5.
STATUS/CONTROL CONNECTOR
1
Door opens
and door sensor
opens contacts.
the door is open, and activates a remote device,
3
4
Alarm module activates a relay contact closure
(for 30 seconds) and activates remote device,
In situations where a remote sensor input to the 4500 Alarm module indi-
cates a condition that requires external intervention, such as when the tem-
perature in the CO exceeds a predefined limit and supplemental air condi-
tioning is required, the 4500 Alarm module provides four relays that can be
connected to supplemental devices to allow the NOC operator to activate
them by sending activation commands by way of the 4500 Alarm module.
Chapter 2 Module Description
Alarm Module
2
Contact open
reported by Alarm module.
5
Operator reads trap message that indicates
such as a security camera, using one of
the Control Outputs (1-4) that appear
in the Alarm Module Configuration window.
6
such as a security camera.
Functional Description
15 Status inputs
(for example,
door, fan,
thermometer)
4 Control
Output
Relays
Release 10.0.0
2-7