Power Specifications - IBM 2109 Model M12 User Manual

Table of Contents

Advertisement

v An air flow of at least 350 cubic feet per minute per switch, available in the
v The power specifications listed in "Power specifications".
v The environmental specifications listed in "Environmental requirements" on
v Interference less than the standard levels listed in Table 15 on page 22, under

Power specifications

CAUTION:
To remove power to the 2109 Model M12, disconnect both power cables. (5)
The 2109 Model C36 with Model M12 supports F_port, FL_port, and E_port
connections and distributed name server (DNS). It is electro-magnetic compatibility
(EMC) compliant.
The power supplies are universal and capable of functioning worldwide without
using voltage jumpers or switches. They meet IEC 61000-4-5 surge voltage
requirements and are autoranging in terms of accommodating input voltages and
line frequencies. Each power supply has its own built-in fan for cooling, pushing the
air towards the port side of the chassis.
The power specifications listed in Table 13 are calculated for fully-loaded systems
with four power supplies. A fully-loaded system has eight 16-port cards, two CP
cards, and three blower assemblies.
Table 13 lists the power specifications for the 2109 Model C36 with Model M12.
immediate vicinity of the 2109 Model C36 with Model M12.
page 22.
Immunity.
Table 13. Power specifications
Specification
Total power available from each power
supply
Input voltage
Input line frequency
Harmonic distortion
Heat output (BTU rating)
Maximum inrush current per power cord
Input line protection
Power supply dimensions
Value
1 KW
200 - 240 V ac
50 - 60 Hz
Active power factor correction per
IEC1000-3-2
v 64 ports: 1080 watts, 3690 BTU per hour
v 128 ports : 1960 watts, 6700 BTU per
hour
40 amps Peak
Thermal circuit breaker
6.96 cm (2.74 in.) wide, 12.34 cm (4.86 in.)
high, 34.29 cm (13.50 in.) long
Appendix A. Product specifications
21

Advertisement

Table of Contents
loading

Table of Contents