Section H: Control Circuit Terminals

H1 Digital Inputs

F9-06 Bus Fault Select
The setting of parameter F9-06 selects the stopping method when an BUS fault is detected.
A BUS fault may occur when using the SI-B or the CP-916 communication options. The fault will
occur after initial communication has been established then the connection is lost. The following fault
code will be displayed: "BUS SI-B Com Err".
H
Control Circuit Terminal Parameters
H1
Digital Inputs
The VS-616G5 has six multi-function contact inputs for the set-up of numerous functions, including
multi-step speed operation, PID, speed search, speed/torque control selection, and many other. This
section includes descriptions of these functions.
H1-01 Multi-function Input Terminal 3 Selection
H1-02 Multi-function Input Terminal 4 Selection
H1-03 Multi-function Input Terminal 5 Selection
H1-04 Multi-function Input Terminal 6 Selection
H1-05 Multi-function Input Terminal 7 Selection
H1-06 Multi-function Input Terminal 8 Selection
The following table lists the function selections for the multi-function contact inputs (terminals 4 to 8),
and indicates the control modes during which each function can be enabled.
H1-01
to 6
Setting
0
3-Wire Control
1
Local/Remote Selection
2
Option/Inverter Selection
3
Multi-Step Ref. 1 (factory default, H1-03)
4
Multi-Step Ref. 2 (factory default, H1-04)
5
Multi-Step Reference 3
6
Jog Frequency Ref. (factory default, H1-05)
7
Multi-Accel/Decel 1
8
Ext. Baseblock N.O. (factory default, H1-06)
9
External Baseblock N.C.
A
Accel/Decel Ramp Hold
B
OH2 Alarm Signal
C
Terminal 16 Enable
D
V/f Mode Selection
E
ASR Integral Reset
10
MOP Increase
11
MOP Decrease
76
Setting
0
Ramp to Stop - Ramp to stop according to C1-02 set value.
1
Coast to stop.
2
Fast-Stop - Ramp to stop according to C1-09 set value.
3
Alarm Only - Alarm flashes, operation continues.
Function
Bus Fault Sel
Description
Terminal 3 Sel
Terminal 4 Sel
Terminal 5 Sel
Terminal 6 Sel
Terminal 7 Sel
Terminal 8 Sel
Control Method (A1-02)
Open Loop
V/f
V/f w/ PG
Vector
Open Loop
V/f
V/f w/PG
Vector
A
A
A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
Reference
Flux Vector
Page
VS-616G5 Programming Manual
Flux
Vector
A
B
B
B
B
B
B