E2
Motor Set-up
E2-01 Motor Rated Current
Sets the motor rated current in units of 0.01A for inverter models 27P5, 47P5 and smaller; 0.1A for
models G5U2011, G5U4011 and larger. The default setting varies depending on the inverter model set-
ting (O2-04).
E2-02 Motor Rated Slip Frequency
Setting range:
Sets the motor rated slip frequency in units of 0.01Hz. The default setting varies depending on the
inverter model setting (O2-04). Use the following equation to calculate the motor rated slip frequency:
where:
f
s
f : rated frequency (Hz)
N : rated motor speed (rpm)
P : number of motor poles
E2-03 Motor No-Load Current
Sets the motor no-load current in units of 0.01A for inverter models 27P5, 47P5 and smaller; 0.1A for
models G5U2011, G5U4011 and larger. The default setting varies depending on the inverter model set-
ting (O2-04).
E2-04 Number of Motor Poles
Setting Range:
Factory Default:
Sets the number of motor poles.
E2-05 Motor Terminal Resistance
Sets the motor phase-to-phase resistance value in units of 0.01W.
Motor Terminal Resistance =
The default setting varies depending on the inverter model setting (O2-04).
VS-616G5 Programming Manual
0.00 to 20.00Hz
f s
: slip frequency (Hz)
2 to 48 poles
4 poles
Phase-to-Phase Resistance at
Insulation Class Temperature
Motor Rated FLA
Motor Rated Slip
(
)
N P
=
f
---------------- -
120
No-Load Current
Number of Poles
Term Resistance
273 + (25ºC + insulation class temperature) / 2
×
273 + insulation class temperature
Section E: Motor Parameters