Custom V/f Pattern
Set up a custom V/f pattern by setting parameter E1-03 to "F", and then setting the values in parame-
ters E1-04 to E1-13.
E1-04 Maximum Frequency
E1-05 Maximum Voltage
E1-06 Motor Base Frequency
E1-07 Middle Output Frequency A
E1-08 Middle Output Voltage A
E1-09 Minimum Output Frequency
E1-10 Minimum Output Voltage
E1-11 Middle Output Frequency B
E1-12 Middle Output Voltage B
E1-13 Motor Base Voltage
Be sure to satisfy the following conditions for setting
parameters E1-04 to E1-13:
E1-09 ≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04
* For 460V class units, the value is twice that of 230V class units. For 575V class units the value is 2.5 times the 230V value.
Increasing the voltage in the V/f pattern increases motor torque. However,
V/f pattern, increase the voltage gradually while monitoring the motor current, to prevent
· Inverter fault trips as a result of motor overexcitation
· Motor overheat or excessive vibration
VS-616G5 Programming Manual
Max Frequency
Max Voltage
Base Frequency
Mid Frequency A
Mid Voltage A
Min Frequency
Min Voltage
Mid Frequency B
Mid Voltage B
Base Voltage
E1-05 V
E1-12 V
E1-13 V
E1-08 V mid A
E1-10 V
Figure 28 Custom V/f Pattern Setting
Section E: Motor Parameters
V/f
Voltage
max
MidB
midB
Base
base
MidA
Min
min
0 F
Fmid A F
min
base
E1-09 E1-07 E1-06 E1-11 E1-04
when setting a custom
E1 V/F Pattern
Open Loop
Flux
V/f w/PG
Vector
Vector
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
A
Q
Q
A
Q
Q
Q
A
Q
Q
A
A
A
A
A
A
A
A
A
A
A
Q
Q
Max
Frequency
F
F
midB
max
:
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents