Section H: Control Circuit Terminals
H3 Analog Inputs
H3-04 Terminal 16 Signal Selection
Selects the type of voltage signal input at terminal 16.
The resolution of terminal 16 is 11 bit.
H3-05 Terminal 16 Multi-function Selection
The following table lists the function selections for the multi-function analog inputs (terminals 14 and
16), and indicates the control modes during which each function can be enabled.
Setting
0
Aux. Frequency Ref. (factory default)
1
Frequency Gain
2
Frequency Bias
4
Voltage Bias
5
Accel/Decel Change
6
DC Injection Braking Current
7
Overtorque Level
8
Stall Prevention Level
9
Reference Lower Limit
A
Jump Frequency
B
PID Feedback
C
PID Reference Bias
D
Frequency Reference Bias 2
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque Limit
13
Torque Reference
14
Torque Compensation
15
Forward/Reverse Torque Limit
1F
Not Used
96
Setting
0
0 to 10V input (factory default)
1
-10 to +10V input
Function
V/f
<1110>
<1110>
Terminal 16 Sel
Description
Terminal 16 Sel
Control Method (A1-02)
Open Loop
V/f w/ PG
Vector
Vector
VS-616G5 Programming Manual
B
B
B
B
B
B
Setting Level
Flux
±100% / ±10V
100% / 10V
±100% / ±10V
100% / 10V
100% / 1V
100% / 10V
100% / 10V
100% / 10V
100% / 10V
100% / 10V
±100% / ±10V
10V/Fmax
10V/Fmax
100% / ±10V
100% / ±10V
100% / ±10V
±100% / ±10V
±100% / ±10V
±100% / 10V